Škoda / Karoq (NU) / 08 - Air-conditioning AC Clima [EV_ACClimaBHBVW37X 006146] / Compressor run-in (air condition compressor - replacement)
Search:Search area:
Mark
Model
Control unit
Diagnostic operation
Displayed 1-20 records out of 100.
<< < 1 > >>
Mark
Model
Control unit
Diagnostic operation
Diagnostic procedure
This operation was considered useful 1x.
You are not logged! System works in DEMO mode only now where numbers are replaced with X characters. For 49 EUR only You will get access into full system. You can pay by credit card or bank transfer. Click BUY button for purchase and You will get login to diagnostic procedures database imediatelly.
Conditions:
- learning the end stops of the flaps (basic settings) - Successfully completed
- load management - inactive
- error memory - faultless
- air-conditioning vents - open
- engine speed: idling
- do not switch-off the ignition and do not break the communication
- ventilation: ON
Note: done after replacement of component: air condition compressor
connect with the control unit XX - air-conditioning
XX - Adaptation
select item in drop-down menu: IDEXXXXX - Duration of compressor run-in
(For easier search in the menu, enter the code IDE, ENG or MAS into the "Filter" window )
enter value: XX s
Start
select item in drop-down menu: IDEXXXXX - Duration of the compressor run-in basic settings
(For easier search in the menu, enter the code IDE, ENG or MAS into the "Filter" window )
enter value: XXX s
Start
XX - Actuators
select item in drop-down menu: IDEXXXXX - Adoption of exterior unfiltered temperature
Start
wait XX s
XX - Measured values
select item: IDEXXXXX - ambient temperature select item: IDEXXXXX - ambient temperature - calculated value
(For easier search in the menu, enter the code IDE, ENG or MAS into the "Filter" window )
desired condition: ambient temperature = ambient temperature - calculated value
XX - Basic settings
select item in drop-down menu: IDEXXXXX - Compressor run-in
activate default settings
wait: XXX s
End basic set-up
XX - Adaptation
select item in drop-down menu: IDEXXXXX - Duration of the compressor run-in basic settings
(For easier search in the menu, enter the code IDE, ENG or MAS into the "Filter" window )
enter value: XX s
Start
check of error memory
desired condition: faultless
XX - end of communication
You are not logged! System works in DEMO mode only now where numbers are replaced with X characters. For 49 EUR only You will get access into full system. You can pay by credit card or bank transfer. Click BUY button for purchase and You will get login to diagnostic procedures database imediatelly.